Products details

LCD Three Phase Digital Multifactional Power Instrument

  • Category : Digital Meter
  • Tel : +86-577-62627957
  • Email : 1273444947@qq.com
  • Fax : +86-0577-62627466
Technical parameters
Measuring range:
●Phase voltage(U A , U B , U C) :0~500V
●Line voltage(U AB , U BC , U CA) :0~500V
●Current(I A , I B , I C) :0~9999A
●Freuqency :45~65Hz
●Power factor(PF A , PF B , PF C , PF S) :0.0C~1.0~0.0L
●Active power(P A , P B , P C , P S) :0~999W~999KW~9999MW
●Reactive power(Q A , Q B , Q C , QS) :0~999Var~999KVar~9999MVar
●Apparent power(S A , S B , S C , S S) :0~999VA~999KVA~9999MVA
●Active electric energy : 0~999Wh~999KWh~9999MWh
●Reactive electric energy : 0~999Varh~999KVarh~9999MVarh
Communication interface:RS485 serial communication,applying MODBUS_RTU communication protocol.
Accuracy rating:±0.5 % FS±1 digit.
Signal input: Voltage :AC 0~500V(PT */ 100V) ,Current :AC 5A (CT */ 5A )
Sampling rate: about 1 times/s.
Measuring display mode: RMS measurement, four-digit LED nixietube display.
Display resolution: Max. Display resolution : 0.001A , 0.1V , 0 . 01Hz , 0 . 001PF , 0 . 1W.
Input circuit consumption: current<0.5VA,voltage<1VA
Auxiliary power supply: AC 220V,50/60Hz(Can customize other values).
Auxiliary supply consumption:< 3VA.

Additional functions
4-channels switch value output: Higher and lower limit alarm output by two groups of reply, contact rating
is AC250V/0.1A、DC30V/0.1A.
4-channels switch value input: 4 ways dry contact input port,inside of the instrument there is power supply of +5V.
4-channels analog quantity output: can be set freely as DC 0~10V、0~20mA or 4~20mA, accuracy rating is ±0.5 % FS, electrical isolation between the signal input and auxiliary power supply ,transmitting output load resistance:≤500Ω
Power quality analysis:
● Voltage harmonic distortion rate : THDU
●Current harmonic distortion rate :THDI
● Three - phase voltage unbalanse : ε U
●Three - phase current unbalanse: εΙ.

DISPLAY MODE





A - phase current :5 .200A

A - phase voltage :220 .1V

A - phase active power :1 .100KW

A - phase power factor :1 .000

A - phase apparent power :1 .100KVA

B - phase current :5 .197A

B - phase voltage :220 .0V

B - phase active power :1 .100KW

B - phase power factor :1 .000

B - phase apparent power :1 .100KVA

C - phase current :5 .198A

C - phase voltage :220 .3V

C - phase active power :1 .100KW

C - phase power factor :1 .000

C - phase apparent power :1 .100KVA

Frequency :50 .00Hz

Frequency :50 .00Hz

Total active power :1 .100KW

Total power factor :1 .000

Total apparent power :3 .300KVA

Positive active energy :0 .09KWh

Positive reactive energy :0 .02KVarh

Opposite active energy :0 .09KWh

Opposite reactive energy : 0 .02KVarh



A - phase reactive power :0 .000KVarh

voltage harmonic distortion rate THDU

Current harmonic distortion rate THDI

Three -phase voltage

Three -phase current

B - phase reactive power :0 .000KVarh

A - phase :5 . 28%

A - phase :9 . 88%

unbalance value ε U :0 . 02%

unbalance value ε I :0 . 04%

C - phase reactive power :0 .000KVarh

B- phase :4 . 22%

B- phase :0 . 65%

Positive active energy : 0 .09KWh

Positive active energy :0 .09KWh

Total reactive power :0 .000KVarh

C- phase :3 . 60%

C- phase :0 . 33%

Opposite active energy :0 .09KWh

Positive active energy :0 .09KWh

Positive active energy :0 .09KWh


Model and dimension(unit :mm)


Terminal arrangement
Attention : If it is not the same with the wiring schema of diagram behind case , please accord to the one of diagram behind case.


Typical connection

Welcome to our website. If you have any requests or suggestions,please feel free to email us at 1273444947@qq.com or use the following enquiry form. Please allow us to provide you with the best service.